Reference for US International Building Code (IBC) occupancy types, construction types, height/area limits, egress requirements, and R-2 residential standards. Use when: generating US-compliant building models, validating building designs against IBC, understanding occupancy classifications and construction types.
Structured reference for the US International Building Code (IBC) 2021 and International Residential Code (IRC). Use it to validate building designs, generate code-compliant models, and understand occupancy and construction type constraints. Covers common residential and mixed-use scenarios including occupancy classifications, construction types, height/area limits, egress requirements, and sprinkler systems.
Without sprinklers / With NFPA 13 sprinklers (+1 story, +20 ft):
| Construction Type | Stories (no sprinkler / sprinkler) | Height ft (no / sprinkler) |
|---|---|---|
| V-B | 3 / 4 | 40 / 60 |
| V-A | 4 / 5 | 50 / 70 |
| III-B | 4 / 5 | 55 / 75 |
| III-A | 5 / 6 | 65 / 85 |
| II-B | 4 / 5 | 55 / 75 |
| II-A | 5 / 6 | 65 / 85 |
| I-B | 11 / 12 | 160 / 180 |
| I-A | Unlimited | Unlimited |
A developer is designing a mixed-use building with apartments on floors 2-4 and a restaurant on the ground floor. They need to determine the correct IBC occupancy classifications.
Building use analysis:
Floors 2-4: 12 apartment units (permanent residents, lease > 30 days)
-> R-2 (Multi-family residential, permanent occupancy)
Floor 1: Restaurant with bar seating for 120 patrons
-> A-2 (Assembly, food/drink consumption)
Result: Mixed occupancy R-2 / A-2
- Must meet the more restrictive requirements of both occupancy types
- Fire separation required between A-2 ground floor and R-2 upper floors (IBC Table 508.4)
- Sprinkler system: NFPA 13 recommended (covers both occupancies)
An architect needs to verify that a 3-story V-B apartment building with NFPA 13 sprinklers meets IBC egress requirements.
Building: R-2, V-B, 3 stories, NFPA 13
Unit sizes: Type A = 834 SF, Type B = 645 SF (6 of each per floor)
Height/story check:
Permitted: 4 stories / 60 ft (V-B + NFPA 13)
Actual: 3 stories / 35 ft
-> PASS
Travel distance check:
Maximum permitted: 125 ft (R-2, not increased with sprinklers)
Actual longest path: 66 ft (Level 2, far unit to nearest stair)
-> PASS
Exit access doorways:
Type A (834 SF > 500 SF): 2 exit access doorways required -> PASS (has 2)
Type B (645 SF > 500 SF): 2 exit access doorways required -> PASS (has 2)
Stair width:
Occupant load per floor: (6 x 5) + (6 x 4) = 54 occupants
54 > 49 -> 44" minimum stair width required
Actual: 44" -> PASS
Overall: ALL EGRESS REQUIREMENTS MET